9.3.3 ENCLOSURE GROUNDING AND BONDING
Enclosure grounding and bonding should comply with the following requirements: (See Figs. 9-1
thru 9-3)
1) Have a common grounding or bonding bus (normally a cabinet rail).
RACK CABINET
Cabinet rails used for
bonding/grounding
chassis
These chassis shall be
Bonding Conductor
bonded/grounded internally
from the ground wire in cord
Identified equipment
ground points.
Required for
these chassis.
Bonding Conductor
NRTL listed or labeled
Power Distribution Unit
Required bonding/grounding
Note: Chassis or equipment
(Same gauge or larger
drawing current from the
than AC power cable)
Power Distribution Unit
AC Outlets
within the rack is called
Utilization Equipment
Neutral
3 Phases
Ground
Protective cover
removed from
connection box
Compression
Clamp
AC power cable
Note: This drawing represents typical 120/208 Volt,
Three Phase Wye, 5 wire, ac power.