RACK #1
RACK #2
Cabinet rails used
for bonding.
AC power strip.
Bonding Conductor
These chassis shall be
bonded/grounded internally
Identified
from the ground wire in cord.
equipment ground
points.
Bonding Conductor
These chassis shall be
Identified
bonded/grounded internally
equipment ground
from the ground wire in cord.
points.
Required ground or
bonding wire common
to the ground wire of
Required
the power strip and the
bonding/grounding.
ground wire of the ac
Power
(Same gauge or larger than
power cable coming
Distribution
ac power cable.)
Unit
into this second rack.
"Rack #1" supplying single phase,
(Same gauge or larger
ac power to "Rack #2".
AC
Outputs
than the ac power cable.)
NOTE: This drawing represents a typical
120/208 Volt, three phase Wye, 5 wire,
ac power for Rack #1.
Metallic case of typical power strip
is bonded to the grounding conduct
conductor
through means of mounting screw.
Typical configuration for
Energized conductor - Black
bonding/grounding wire
(Hot, AC source)
going to cabinet rail.
Grounded conductor - White
(Neutral, AC return)
Compression
Equipment grounding conductor -
Grommet
fitting
Green
Green, Green with Yellow stripe, Bare
(Not "NM" type)
(Ground)
The Equipment Grounding Conductor and
Black
shall T
NO
the Grounded Conductor shall NOT
White
Typical Single-Phase, AC plug
be connected together at power cable
for power to"Rack #2".
Incoming ac power
termination.
(Typically, 120 V,
Single Phase)
FIGURE 1 2
Figure 9-2