|
| DOE-HDBK-1092-98
4.7.2 EXCEPTIONS TO NEC 250-94
There is an exception to the main rule. It has three parts and pertains to specific types of grounding
electrodes. The exception applies to grounded and ungrounded systems.
Exception (a) applies to made electrodes only, such as rod, pipe, or plate electrodes. The grounding
electrode conductor is not required to be larger than #6 copper or #4 aluminum.
Exception (b) to NEC Section 250-94 requires at least a #4 copper conductor to be used as a
grounding electrode conductor to ground the electrical system to a concrete-encased electrode.
Exception (c) requires at least a #2 copper conductor to be used as a grounding electrode conductor
to ground the electrical system to a ground ring. [See NEC Section 250-81(d)]
4.8 MAIN BONDING JUMPER
The primary function of the main bonding jumper is to connect the grounded circuit conductors and
the equipment grounding conductors at the service equipment. The main bonding jumper serves as
the main link between the system grounded conductors and the grounding electrode system where
metal equipment enclosures and raceways are utilized to enclose conductors and components. If the
main bonding jumper is left out, there is not a complete circuit for fault current and is an invitation
to a dangerous situation.
The main bonding jumper shall connect together the following items:
1. Grounded conductors and grounded terminal
2. Equipment grounding conductors and grounding terminal
3. All metal enclosures enclosing conductors and components.
If supplied, the manufacturers main bonding jumper is the preferred conductor to be used as the main
bonding jumper. NEC Section 250-79(a) requires the main bonding jumper to be a (1) wire, (2)
screw, (3) busbar, or (4) a similar suitable conductor.
NEC Section 250-79(d) requires the main bonding jumper to be at least the same size as the
grounding electrode conductor where the circular mils rating of the service entrance conductors does
not exceed 1100 kcmil for copper or 1750 kcmil for aluminum.
For example: What size main bonding jumper is required to ground the metal enclosure of the service
equipment to the grounding terminal bar where the service entrance is made up of one #250 kcmil,
THWN copper conductor per phase?
4-10
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |