|
| DOE-HDBK-1092-98
Step 1:
Finding the largest phase--NEC 250-79(d) #250 kcmil is the largest phase
Step 2:
Finding the bonding jumper--Table 250-94 #250 kcmil requires #2 copper
Answer:
The size of the main bonding jumper (GEC) is at least #2 copper.
Where the kcmil rating of the service entrance conductors exceeds 1100 kcmil for copper or 1750
for aluminum, the bonding jumper shall be at least 12 l/2% of the largest kcmil rating of any one
phase.
For example: What size main copper bonding jumper is required for a service entrance with a makeup
of 2400 kcmil copper conductors per phase?
Step 1:
Finding the largest phase--NEC 250-79(d) 2400 kcmil x 0.125 = 300 kcmil
Step 2:
Finding the main bonding jumper--NEC Table 250-94; Table 8, Ch. 9 requires
300 kcmil
Answer:
The main bonding jumper is required to be at least 300 kcmil copper.
Note: In this case the main bonding jumper is greater in size than the grounding electrode conductor,
which is only required to be #3/0 copper per NEC Table 250-94 based upon the 2400 kcmil copper
conductors.
4.9 SYSTEM WITH GROUNDED CONDUCTOR
The main purpose of the grounded conductor is to carry unbalanced neutral current or fault current
in the event that one phase should go to ground.
Note: The grounded conductor does not always have to be a neutral conductor. It is a phase conductor
when used in a corner grounded delta system.
In solidly grounded service-supplied systems, the equipment grounding conductors shall be bonded
to the system-grounded conductor and the grounding electrode conductor at the service equipment.
The grounded conductor may be used to ground the noncurrent-carrying metal parts of equipment
on the supply side of the service disconnecting means per NEC Section 250-61(a). The grounded
conductor can also serve as the ground-fault current return path from the service equipment to the
transformer that supplies the service.
The grounded conductor shall not be used to ground the metal parts of enclosures enclosing
conductors and components on the load side of the service per NEC Section 250-61(b). See NEC
4-11
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |