|
| DOE-HDBK-1092-98
working space shall be 3 ft, 3 1/2 ft, or 4 ft, depending upon existing conditions. The conditions are
as follows:
Condition 1: These are exposed live components on one side of a space and ungrounded parts on the
other side.
Condition 2: The electrical equipment is mounted or set on one wall, and the wall on the opposite
side is grounded. If the qualified worker should accidentally contact the conductive wall while
touching live components, a circuit would be completed to ground and a fatal shock might occur.
Condition 3: The electrical equipment is mounted or set on one wall, and additional electrical
equipment is mounted or set on the opposite side of the room. There are live components on both sides
of the room. The qualified worker might accidentally make contact with live components and be in
series with a hot phase and the grounded metal of the electrical equipment, which could produce a
fatal shock.
See Figure 2-3 for the clearance requirements in front of electrical equipment rated 600 V or less.
See NEC Section 110-16(a) Exception 1 for clearance requirements in the rear of electrical
equipment.
Electrical
equipment
opposite
No live or
electrical
Grounded
grounded
equipment
parts
parts
Electrical
Electrical
equipment
equipment
Min.
Min.
Min.
dist.
dist.
dist.
Condition 2
Condition 3
Condition 1
Volts to ground Min. dist. Volts to ground Min. dist. Volts to ground Min. dist.
0 - 150 V
3 ft.
0 - 150 V 3 ft.
0 - 150 V
3 ft.
151 - 600 V
3 ft.
151 - 600 V 3 1/2 ft. 151 - 600 V
4 ft.
L93 0350
NEC Table 110-16 (a)
OSHA Table S-1
Figure 2-3. Minimum clearances in front of electrical equipment (600 V or less).
2-13
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |