|
| DOE-HDBK-1092-98
2.9.2 ELECTRICAL EQUIPMENT RATED OVER 600 VOLTS
NEC Section 110-34(a) and Table 110-34(a) list the minimum clearance required for working spaces
in front of high-voltage electrical equipment such as switchboards, control panels, switches, circuit
breakers, switchgear, motor controllers, etc.
There are three conditions to apply as in NEC Section 110-16(a) and Table 110-16(a)
1. Where there are exposed live components on one side of a space and no live or ungrounded
parts on the other side.
2. Where there are exposed live components on one side and grounded parts on the other such
as concrete, brick, and tile walls that are considered to be grounded parts.
3. Where there are exposed live components on both sides.
See Figure 2-4 for the clearance requirements in front of electrical equipment rated at over 600 V.
See NEC Section 110-34(a) Exception for clearance requirements in the rear of electrical equipment.
Electrical
equipment
opposite
electrical
No live or
Grounded
equipment
grounded
parts
parts
Electrical
Electrical
equipment
equipment
Min.
Min.
Min.
dist.
dist.
dist.
Condition 1
Condition 2
Condition 3
Volts to ground
Min. dist.
Volts to ground
Min. dist.
Volts to ground
Min. dist.
601 - 2,500 V
3 ft.
601 - 2,500 V
4 ft.
601 - 2,500 V
5 ft.
2,501 - 9,000 V
4 ft.
2,501 - 9,000 V
5 ft. 2,501 - 9,000 V
6 ft.
9,001 - 25,000 V
5 ft.
9,001 - 25,000 V
6 ft. 9,001 - 25,000 V
9 ft.
25,001 - 75,000 V
6 ft.
25,001 - 75,000 V
8 ft. 25,001 - 75,000 V 10 ft.
above 75,000 V
8 ft.
above 75,000 V 10 ft. above 75,000 V 12 ft.
L93 0349
NEC Table 110-34
OSHA Table S-2
Figure 2-4. Minimum clearances in front of electrical equipment (over 600 V).
2-14
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |