8.1.10.4 NONMETALLIC SHEATHED CABLE
Nonmetallic sheathed cable shall be used as allowed by the NEC and as follows:
1. Along studs, joists, or similar supports closely following the building finish or running boards
when 7 ft 8 in. or more above the floor
2. When firmly attached to each cabinet, box, fitting, or fixture by means of a cable clamp.
Nonmetallic sheathed cable shall not be used where precluded by the NEC as follows:
1. As portable extension cords
2. Lying on the ground subject to any type of traffic
3. Where subject to frequent flexing
4. As service entrance cable.
See Figure 8-1 for a detailed illustration of installing temporary wiring methods. NOTE: The 1996
NEC does not permit open wiring or conductors except as allowed in NEC Section 305-4(b) and (c)
Exceptions.
NEC Article 305
OSHA Sections 29 CFR 1910.305(a) and 1926.405(a)
Figure 8-1. Cables, cable assemblies, or multiconductor cords can be used for temporary wiring systems under
certain conditions of use.