Click here to make tpub.com your Home Page

Page Title: Exposed Sockets and Broken Bulbs
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-HDBK-1092-98
Portable electric lighting used in confined wet or hazardous locations such as drums, tanks, vessels,
and grease pits shall be operated at a maximum of 12 V, be intrinsically safe, or be protected by a
GFCI circuit.
8.1.8 EXPOSED SOCKETS AND BROKEN BULBS
Exposed empty light sockets and broken bulbs shall not be permitted. This rule is to protect personnel
from accidentally contacting the live parts in the socket and being shocked.
8.1.9 GROUND FAULT PROTECTION FOR PERSONNEL
Temporary power to equipment used by personnel shall be protected by GFCI devices, where
required, or included in an assured equipment grounding conductor program, where permissible. See
NEC Section 305-6, 29 CFR 1926.404(a)(3)(b), Sections 2.7 and 8.3 for further information.
8.1.10 WIRING METHODS
The requirements for temporary wiring for power and lighting purposes include provisions for wire
connections, junction boxes, and overcurrent protection, as well as the use of conductors. See NEC
Article 305.
8.1.10.1 SERVICE CONDUCTORS
Service conductors shall comply with all the provisions of Article 230 in the NEC when they are used
as wiring methods to supply temporary power systems.
8.1.10.2 FEEDER CONDUCTORS
Feeders are the conductors that transmit power from the service equipment to the distribution
panelboard or between the main disconnect and the branch circuit over current devices (circuit
breakers, fuses). Feeders for temporary wiring shall originate inside an approved distribution center,
such as a panel board, that is rated for the voltages and currents the system is expected to carry. Some
equipment is manufactured specifically for temporary use.
Feeders can be run as cable assemblies, multiconductor cords, or cables with two or more conductors
each with their own insulations, run together in the same cord or cable.
8.1.10.3 BRANCH CIRCUIT CONDUCTORS
Branch circuits are the conductors between the last overcurrent device in an electrical system and the
outlets, such as receptacles, lighting outlets, and outlets for electrical equipment wired directly into
a circuit. Branch circuits for temporary wiring shall originate inside an approved panelboard or
power outlet that is rated for the voltages and currents the system is expected to carry. As with feeders,
branch circuit conductors can be contained within multiconductor cord or cable assemblies.
8-3


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business