8.1.3 WET LOCATIONS
Conductors with nonrated weather-proof insulation shall not be enclosed in metal raceways or used
for wiring in tanks, penstocks, or tunnels. Receptacles used in damp or wet locations shall be
approved for the purpose. When a receptacle is installed outdoors (outdoors is considered a wet
location), it shall be contained in a weatherproof enclosure, the integrity of which would not be
affected when an attachment plug is inserted.
All temporary lighting strings in outdoor or wet locations, such as tunnels, culverts, valve pits,
outlets, and floating plants, shall consist of lamp sockets and connection plugs permanently molded
to the hard service cord insulation.
8.1.4 SUPPORTS
Bare or open conductors shall be insulated from their supports. This requirement prevents arcing,
sparking, or flash-over to grounded objects. Open wiring for temporary installations is only allowed
as per NEC Section 305-4(b) and (c) Exceptions.
8.1.5 CONDUIT
Temporary wiring installed in conduit shall have bushings at all outlets and terminals to prevent
abrasion and damage to the insulation.
8.1.6 LIGHTING
All lamps for general illumination should be protected from accidental contact or breakage. Metal-
case sockets shall be grounded.
Temporary lights shall not be suspended by their electric cords unless cords and lights are designed
for this means of suspension. Temporary lighting used in damp, wet, or hazardous areas shall be
marked as suitable for use in those locations.
Portable electric lighting used in wet or other conductive locations (for example, drums, tanks, and
vessels) shall be operated at 12 V or less. However, 120-V lights may be used if protected by a ground
fault circuit interrupter (GFCI).
Receptales on construction sites shall not be installed on branch circuits that supply temporary
lighting. [See NEC Section 305-4(d)]
8.1.7 CONFINED SPACES
When temporary wiring is used in tanks or other confined spaces, an approved disconnecting means
(identified and marked) shall be provided at or near the entrance to such spaces for cutting off the
power supply in emergencies.