| DOE-HDBK-1092-2004
3. They shall have both circuit conductors insulated from the frame and all other grounded
surfaces.
in NEC 250.6 and 305.6 (a), EX.
Figure 6-3. The ungrounded frame of a generator is acceptable as a grounding electrode
if the circuit conductors are insulated from the frame and all other grounded surfaces.
6.5
BATTERIES
Storage batteries are considered a live source and appropriate precautions should be taken
when working around them. Information regarding batteries and battery rooms can be found in
NESC, NFPA 70E Article 240 and 320.
6.5.1
SURROUNDING SPACE
Adequate space should be provided around storage batteries for safe inspection, maintenance,
testing, and cell replacement. Space shall be left above cells to allow for operation of lifting
equipment when required, for addition of water, and for taking measurements.
6.5.2
LOCATION
Storage batteries should be located in a protective enclosure or area accessible only to qualified
persons. A protective enclosure can be a battery room; a control building; or a case, cage, or
fence that shall protect the contained equipment and minimize the possibility of inadvertent
contact with energized parts.
6.5.3
VENTILATION
The battery storage area shall be ventilated by either a natural or powered ventilation system to
prevent accumulation of hydrogen. The ventilation system shall limit hydrogen accumulation to
less than an explosive level.