|
| DOE-HDBK-1092-2004
Equipment cable/utility runs installed in cable/utility management systems should be visually
inspected periodically. These inspections should be performed at the time of installation and any
interval specified in the equipment documentation. Any inspection should, as a minimum,
consist of:
1. A visual check for the integrity of cable jackets and visible shields;
2. A check for the integrity of all utility hoses by looking and listening for leaks;
3. A visual check on all securing devices used to hold the bundle on the tray to assure the
bundle is positioned properly and no damage has occurred;
4. A visual inspection on all bends for signs of pinching, cutting, exceeding minimum cable
bending radius, or other damage; and
5. Documentation of all results of any inspection.
Supports shall be provided to prevent stress and physical damage to cables where they enter or
exit cable/utility management systems.
9.11 ELECTRICAL SAFETY REQUIREMENTS FOR TESTER
FACILITIES
The following is not intended to encompass all of the electrical design requirements which must
be considered in planning electrical systems for facilities intended to accommodate testers. The
information provided should, however, provide a guide to understanding for personnel who
would be tasked with specifying facility electrical safety necessary to the testing environment.
Provisions for an adequate number of receptacle outlets and associated branch circuits to
accommodate cord and plug connected equipment, testers, etc., in a facility must also be
considered in specifying the electrical requirements.
For equipment that cannot tolerate power interruption, consideration should be given to the use
of a continuously operating or standby uninterruptible power supply (UPS) or a generator.
9.11.1 AMPACITY OF FACILITY WIRING AND DISTRIBUTION EQUIPMENT
Consideration must be given to accommodating the anticipated load demand which may occur
as a result of power supplied to the various possible combinations of electrical equipment
connected to a particular branch circuit (See Section 9.4).
9.11.2 FACILITY GROUNDING AT TEMPORARY OR REMOTE SITES
Proper grounding is considered crucial to providing the safest possible electrical installation,
from the standpoint of maximizing the safety of facility occupants and minimizing property
damage and loss.
Designs for equipment to be used at temporary or remote sites must take into consideration the
same grounding issues which may not be accommodated in the same manner as for permanent
facility power wiring (See Section 9.3 and NEC Article 527).
9-17
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |