| DOE-HDBK-1092-2004
Figure 9-6
9.10.2 REQUIREMENTS
An assessment of any hazards identified with the equipment and the operation with which it is
involved should be performed to assure safe operation of components in the cable/utility
management system. Where any cable/utility runs include hazardous fluids or pressurized
gases, the utilization of these utilities with the cables involved must be determined to be safe.
Metallic cable/utility management systems that support electrical conductors shall be grounded
or bonded to the equipment. Grounding integrity should be checked by inspection by a qualified
worker for all components with exposed metal parts. This inspection should be documented.
Where cable/utility management systems are installed exclusively for electrical/electronic
equipment usage and where these trays are metallic and not grounded or bonded, approved
documentation shall exist stating the reason for not grounding or bonding the system (See
Section 9.3.1).