| DOE-HDBK-1092-2004
9.3.3
ENCLOSURE GROUNDING AND BONDING
Enclosure grounding and bonding should comply with the following requirements: (See Figs. 9-1
thru 9-3)
Cabinet rails used for
bonding/grounding chassis
These chassis shall be
Bonding Conductor
bonded/grounded internally
from the ground wire in cord
Identified equipment
ground points.
Required for these
chassis.
Bonding Conductor
NRTL listed or labeled Power Distribution Unit
Note: Chassis or equipment drawing current
Required bonding/grounding
from the Power Distribution Unit within
(Same gauge or larger than
the rack is called Utilization Equipment
AC power cable)
AC Outlets
Protective cover
removed from
connection box
Compression
AC power cable
Clamp
Note: This drawing represents typical 120/208 Volt,
Three Phase Wye, 5 wire, ac power.
Figure 9-1
9-3
|