DOE-HDBK-1099-96
APPENDIX B - EXAMPLE DRILL SCENARIOS
Title:
Fire in Diesel Generator Area
Drill Number: 30.94.04.3
Revision Number: 0
Drill Initiation: The drill will be initiated by the Reactor Auxiliary Operator observing smoke in
the diesel generator area. The fire will be from a pile of oily rags piled up on
the floor near the east end of M-43 or west end of M-42 diesel (either diesel
can be used for this drill). M-42 is the running diesel. The standby diesel
generator has just finished having some general maintenance performed on it,
this is the source of the oily rags. The diesel generator area is full of light
smoke but not to the point of a person having to crawl to avoid smoke or
donning Self Contained Breathing Apparatus (SCBA).
Expected Response/Evaluation Criteria:
Circle Yes or No
1) The fire is identified by the Reactor Auxiliary Operator (RAO).
Yes
No
2) The RAO summons the Fire Department and informs the Shift Manager of the
situation.
Yes
No
3) The RAO remotely trips the diesel.
Yes
No
4) The Shift Manager (SM) directs the reactor be shutdown if not already
shutdown.
Yes
No
5) Procedure E-0 out and used.
Yes
No
6) Emergency Brigade responds to the fire in the diesel generator area.
Yes
No
7) SM classifies the event and makes notifications.
Yes
No
B 7-5