|
| DOE-SPEC-3021-97
c. AC-input failure
d. AC-input return
e. Transfer (forward and reverse)
f.
Rated full load
g. UPS efficiency (half and full load)
h. Unbalanced load
i.
Output voltage balance and phase
j.
Overload capability
k. Short-circuit-current capability
l.
Voltage rise
m. Voltage dip
n. Harmonics components
o. Audible noise
No-load/light-load testing. Test the assembled UPS system to verify its capability
6.2.4
to operate continuously under no-load or light-load, as in paragraph 3.3.2.5. The
test duration shall be a minimum of 24 hours.
Surge withstand tests. Conduct surge-withstand capability tests using the
6.2.5
appropriate sections of IEEE C37.90 and IEEE C37.90.1 as a guide. The
surge-withstand test wave shall be oscillatory with a 3000-V crest value in the
first half cycle. The wave shape shall rise from 10 to 90% in 0.5 microsecond,
then decay while oscillating at 100 kHz with each peak being 60% of the
preceding peak as shown in figure 2 of IEEE C62.41.
the Owner to demonstrate performance requirements as specified herein. Any rework
necessary to bring the UPS system into compliance with this specification shall be at
Seller's expense.
Remove all rust, oil, grease, chalk, crayon, and paint marks, and other deleterious material
from all surfaces of the equipment. Touch up any cuts, nicks, or scratches to the coating
system.
29
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |