|
| DOE-STD-1066-99
14.6.2.4
Duct entrance filters may not require fire screens unless a significant
amount of combustible materials are present in the exhaust stream exiting
the duct.
14.7 Detection Systems
14.7.1
Detectors
14.7.1.1
Automatic fire detectors should conform to NFPA 72, "National Fire Alarm
Code."
14.7.1.2
Detectors should be rate compensated type heat detectors.
14.7.1.3
Detectors should be approved for the specified use.
14.7.1.4
operations require higher temperature air flows (see Appendix B for
maximum filter operating temperatures).
14.7.1.5
Existing detectors that are supervised, with suitable, equivalent, and
reliable methods of detection (as determined by the AHJ) that are not rate
compensated type or not listed may continue to be used while they remain
serviceable.
14.7.2
Detector Location
14.7.2.1
Heat detectors or pilot sprinkler heads should be provided in ducting prior
to final filter enclosures. Airflow should be considered when determining
detector or pilot head location.
14.7.2.2
Heat detectors or pilot sprinkler heads should also be provided in the final
filter enclosures.
14.7.2.3
If filter plenum automatic deluge spray systems are actuated by pilot
sprinkler heads, heat detectors are not required in the ducting or the filter
enclosure unless specified by the AHJ.
14.7.3
System Arrangement
14.7.3.1
The detection system or pilot system should be arranged to detect a rise
in air flow temperatures, actuate automatic fire suppression systems, when
required, and transmit an alarm to the responding fire department or
constantly attended proprietary station. The fire alarm system should be
installed per NFPA 72.
14.7.3.2
A pilot operated system should only be used when automatic water deluge
spray systems are required under Section 14.8.
25
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |