|
| DOE-STD-1066-99
14.7.3.3
Control units and signaling alarm systems connected to the heat detectors
should be listed for their intended purpose.
14.7.3.4
Existing detection systems or pilot systems that provide equivalent and
reliable methods of detection and alarm signaling transmission (as
determined by past performance and/or engineering analysis) that are
electrically supervised but are not listed may continue to be used while
they remain serviceable.
14.7.4
Detection Testing Capability
14.7.4.1
Detector installations should be engineered and installed so that they can
be tested during the life of the detector. Remote testing should be
provided for detectors that are not accessible due to unacceptable
hazards. One method of providing remote testing is to provide detectors
with heating strips or coils that can be energized by a separate control
unit. If a line-type heat detection system is used, a heat testing pad
should be provided outside the plenum for operability testing of the
system.
14.7.4.2
Where high contamination levels do not exist, detectors may be installed
so that the detector can be removed from the plenum enclosure and
tested externally.
14.8 Deluge Spray Suppression Systems
14.8.1
Location
14.8.1.1
Automatic and manual water deluge spray systems should be provided
inside all final filter plenums for protection of the filters where they have a
leading filter surface area greater than 16 square feet (1.4 square meters).
14.8.1.2
Automatic water deluge spray systems should be provided inside all final
filter plenums having a leading surface area of 16 square feet (1.4 square
meters) or less when the filter plenum is not separated by fire rated
construction.
14.8.1.3
Plenums that have already been built and are in service before issuance
of these guidelinesare not required to be backfitted with automatic or
manual water deluge spray systems unless there is a significant hazard
that endangers building occupants, the public, or the environment, as
determined by an FHA or as required by the AHJ.
14.8.1.4
The design of water deluge spray systems should reflect the potential for
filter failure mechanisms, such as filter media damage resulting from
weakened media due to water absorbtion and excessive differential
pressures during water discharge. Such failure mechanisms can be
significantly mitigated by throttling back fan controls to reduce the filter
pressure or by providing redundant filters.
26
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |