|
| DOE-STD-1066-99
liquids in any quantity should not be permitted. In addition, the storage of spare filters
inside the filter plenum should not be permitted.
14.5.2
Electrical Equipment Utilized in Final Filter Enclosures
All electrical equipment located in the filter plenum should comply with NFPA 70 and all
electrical wiring located in the filter enclosure should be in metal conduit.
14.5.3
Processes Subjecting Final Filter Plenum to Flammable and Combustible Vapors
14.5.3.1
When operations or processes involve flammable or combustible liquids
that produce vapors, the concentration of the gases or vapors inside the
final filter plenum should not exceed 25 percent of their lower flammable
limit inside the filter enclosure.
14.5.3.2
Fixed combustible gas analyzers should be provided in the final filter
enclosure when the process involves gases or vapor with analyzer alarms
set to sound an alarm at 25 percent of the lower flammable limit. These
alarms should be transmitted to a continuously manned location.
14.5.4
Processes Subjecting Final Filter Plenum to Pyrophoric Dust Particles
When operations or processes involve pyrophoric materials that may subject the final filter
plenum to the pyrophoric dust particles, a method to remove the dust particles before
reaching the final filter enclosure, such as a prefilter, should be required.
14.5.5
Processes Subjecting Final Filter Plenum to High Dust Loading, High Moisture
Air, Acid, or Solvent Environments
Operations sometimes may involve processes that may subject the final filters to airstreams
carrying high moisture content, high dust loading, acids, and solvents that may rapidly
degrade, plug or disintegrate the final filter medium or separators. When operations
involve these sorts of airstreams, preventive methods should be utilized to stop the
degradation impact on the final filters. These can include, but are not limited to, more
frequent filter change outs, prefilters, scrubbers or traps, filters rated for the particular
environment, and the use of alternative chemicals. When chemical degraders to HEPAs
(HCLO4), processes should include scrubbers, traps, or other methods to remove the
chemical before the final HEPA filters.
14.6 Prefilters, Duct Entrance Filters, and Fire Screens
14.6.1
Prefilters and Duct Entrance Filters
Protection of the final filter plenum from dust and particulate loading should be
accomplished by using duct entrance filters or prefilters or a combination of both as follows:
14.6.1.1
All gloveboxes, hot cells, and fume hoods connected to containment
ventilation systems should be provided with at least moderately efficient
23
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |