Figure C.1. Plan Diagram of Filter Plenum Fire Protection
(Diagram for reference purposes only. See written criteria for actual requirements)
1
Water supply may be a limited water supply. Secondary supply may not be required.
2
Pipe drains to either a process waste system or collection tanks.
3
Minimum two stages of HEPA filters required. Additional stages of HEPAs are permitted.
4
Pilot sprinkler heads may be used to activate deluge system. Heat de tection also required in final filter enclosure.