|
| DOE-STD-1066-99
are present and water does not create the possibility of a criticality, then
water should be used.
15.4.1.4 In selecting the type of manual fire extinguishing unit and the application of
extinguishing agent within the glovebox, the designer should consider:
o the potential for glovebox overpressurization;
o the effect of fire extinguishing agent on filters; and
o the potential for increased contamination spread.
15.4.2 Quick-Disconnect Couplings
15.4.2.1 Where manual suppression is the primary fire suppression method for the
glovebox, pre-piped discharge points equipped with quick-connect couplings
should be provided to facilitate the use of portable fire extinguishers. These
couplings should be installed so that the extinguisher discharge is directed
away from the exhaust filtration. (Tests have shown that a single disconnect
coupling supplied by a 5 lb. [2.25 kilograms] dry chemical extinguisher can
cover approximately 18 square feet [1.62 square meters].) Details of a quick
connect coupling are provided in Appendix F.
15.4.2.2 If access is a problem, extension tubes or pipes that extend to accessible
areas should be used to provide coverage for areas where it is difficult to
reach the quick disconnect couplings.
15.4.2.3 Fire extinguishers with bayonet-type connectors may be used when it is not
feasible to install quick-disconnect couplings. However, the designer should
document the basis for not installing quick-disconnect couplings in the
design report.
15.5 Fire Detection Systems
Gloveboxes should be provided with an automatic fire detection system. (Refer to Appendix
E for examples of glovebox fire detection systems.) A separate detection system is not
required if the glovebox is equipped with an automatic fire suppression system that includes
alarm features or an inerting system with alarm features.
15.5.1 The type of fire detection system to be used should be determined based on the
hazards associated with the glovebox and operational needs. Air flow patterns within
the glovebox should be considered when selecting and locating devices.
15.5.2 Fire detection systems should be designed, installed, acceptance-tested, and
maintained in accordance with the applicable NFPA Standards.
15.5.3 If used, spot-type heat detectors should be installed not more than 8 feet (2.4 meters)
apart.
15.5.4 Heat detection-type systems should be provided with remote testing capabilities.
39
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |