|
| DOE-STD-1066-99
o
facilities where required for protection of human life.
5.3.3
Where required by the Safety Analysis Report (SAR), the design of fire protection
systems to withstand seismic events should be in accordance the criteria developed
by the National Fire Protection Association, except as required by other DOE criteria,
such as in Section 7 of this standard.
5.3.4
Fire protection systems, or portions of them, that must function to control effects of
a Design Basis Accident (DBA) event (as determined by safety analysis accident
scenarios) should be designed to be functional for all conditions included in the
accident scenario. This should include both the event initial cause and its
consequences.
5.3.5
When the use of water sprinkler coverage is precluded because of nuclear criticality
or other incompatibility reasons, nonaqueous extinguishing systems (e.g., inert gas,
carbon dioxide, Halon alternatives, etc.) should be used.
5.3.6
Standpipes should be installed in all structures having three levels or more above or
below grade. Standpipe systems should be provided in other structures, such as
those with extensive and complex interior layouts, where deemed necessary by the
DOE Fire Protection AHJ. Standpipes should be designed and installed as Class 1
systems per NFPA 14.
6.
WATER SUPPLY AND DISTRIBUTION SYSTEM CRITERIA
6.1
Demand
6.1.1
Domestic water distribution systems that also serve fire protection requirements
should be designed to satisfy the calculated Fire Hydrant Demand (see Paragraph
6.1.2) and the peak domestic demand. Where no other requirements are applicable,
the peak domestic demand should be based on 2.5 times the calculated average daily
demand plus any special demands, such as industrial or processes that cannot be
reduced during a fire. The distribution system should be capable of meeting this
combined demand at a minimum residual pressure of 20 psi at ground elevation (or
higher elevation if special conditions apply) for a period of not less than 2 hours.
Municipal supplies having the same capability are acceptable.
6.1.2
Fire Hydrant Demand - Where reliance is placed on fire department response, either
for protection of unsprinklered buildings or where the fire department will serve as
redundant (backup) protection, the water supply available from hydrants should be
capable of providing the flow rates established in the Uniform Fire Code based on the
most severe facility fire risk on site. These values may be reduced by a maximum of
50% when the facility is provided with automatic sprinkler protection throughout, in
accordance with the applicable NFPA Standards.
6.1.3
Within a building or facility, domestic water should be supplied by a separate service
line and not be a combined fire protection and potable water service or a combined
process water and potable water system. Where combined fire and domestic-process
water systems are used, distribution piping should be routed and provided with valves
11
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |