Click here to make tpub.com your Home Page

Page Title: System Arrangement
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



DOE-STD-1066-99
such that the domestic and process systems can be isolated without shutting off the
fire system supply.
6.2
System Arrangement
6.2.1
Facilities having a Maximum Possible Fire Loss (MPFL) in excess of $100 million and
significant nuclear facilities (Catagory 1 Hazard) should be provided with an
additional, independent source of fire protection water.
6.2.2
Whenever feasible, all water distribution systems should be of the looped grid type
providing two-way flow with sectional valving arranged to provide alternate water flow
paths to any point in the system. In addition, sectional control valves should be
provided to limit the number of hydrants and individual sprinkler systems made
inoperative during a single line break to a total of five. Dead end runs utilized as a
single supply to fire hydrants should not exceed 300 feet.
6.2.3
Listed and/or approved control valves should be installed at maximum intervals of not
more than 5,000 feet on long supply lines and at maximum intervals of not more than
1200 feet on main distribution loops, feeders and all primary branches connected to
these lines. Such control valves should also be installed at selected points throughout
the distribution system to provide system control over each service area.  At
intersections of distribution mains, one less control valve than the total number of
intersecting mains may be provided. As an aid in determining the minimum number
of sectional control valves, the critical nature of the building/facility should be
considered as well as the number of fire and domestic systems affected in a potential
line failure.
6.2.4
Sprinkler system water supply lead-ins should not run under buildings except for the
minimum distance possible. Sprinkler system risers and alarm valves should be
located as close as practical to a building entry point. Where a riser would otherwise
be located in a potentially contaminated area, consideration should be given to
locating the riser exterior to the building in a heated enclosure.
6.2.5
Hydrants should be provided so that hose runs from hydrants to all exterior portions
of a protected building are no more than 300 feet. Hydrants should not be closer to
than 40 feet to buildings.
7. AUTOMATIC SPRINKLER SYSTEM CRITERIA
7.1
NFPA Standard 13 should be used to determine the occupancy classification for any facility.
For facilities where there is a potential for a change in occupancy, light hazard occupancy
sprinkler system design criteria should not be used.
7.2
Hydraulically designed sprinkler systems should be designed for a supply pressure of at least
10% but not less than 10 psi below the supply curve. (Refer to NFPA Standard 13.)
12


Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business