6. PLACEMENT REQUIREMENTS
6.1 Separation Distances
Relocatable structures should comply with the following separation distances:
Exposing Wall Length
Minimum Separation Distance
ft (m)
ft (m)
10 (3)
20 (6)
20 (6)
30 (9)
30 (9)
35 (11)
40 (12)
40 (12)
50 (15)
45 (12)
60 (18)
50 (15)
More than 60 (18)
60 (18)
The following adjustments of the separation distances specified above are cumulative, but the
minimum distance should not be less than 10 feet (3 meters):
a.
50 percent reduction for light fire loading, e.g., 8,000 BTU/sq. ft. or less.
b.
50 percent increase for heavy fire loading, e.g., 160,000 BTU/sq. ft. or higher.
c.
50 percent reduction for limited supply suppression system in the exposing relocatable
structure which completely protects the structure.
d.
75 percent reduction for an automatic sprinkler system in the exposing relocatable
structure.
e.
75 percent reduction for exposure deluge system.
Exception 1:
This separation distances requirement does not apply if the MPFL of the relocatable
structure combined with all exposed structures is less than $1 million.