| DOE-STD-3003-2000
8)
Correct the hydrometer reading for level and temperature and enter on Data
Sheet 1 as specific gravity.
____
9)
Measure and record the electrolyte level (as found) for each cell. Read from
the bottom of the electrolyte High Level line.
Above line: Add;
Below line: Subtract.
Completed by ____________________________________ Date_______
/
(signature)
(print name)
10)
Inspector shall verify the values obtained in Steps C.8 and C.9.
Verified by ______________________________________ Date_______
/
(signature)
(print name)
11)
If any cell's electrolyte level is below the Low level mark, add distilled water
to those cells to the High level mark, and place on equalize charge per
Battery Equalize Procedure immediately after completion of this procedure.
____
12)
Measure and record the electrolyte level (as left) for each cell. Read from
the bottom of the electrolyte High Level line.
Above line: Add;
Below line: Subtract.
Completed by ____________________________________ Date_______
/
(signature)
(print name)
13)
Inspector shall verify that the Acceptance Criterion in Step C.12 was met.
Verified by ______________________________________ Date_______
/
(signature)
(print name)
Section C completed by ______________________________________________
/
(signature)
(print name)
Date/Time Completed ____________________________ a.m./p.m.
/
: