| DOE-STD-3003-2000
C. BATTERY AND CHARGER CHECK
NOTE: Data from applicable Step(s) in this section shall be recorded on Data
Sheet 1.
1)
Check and record Battery Charger voltage (as found) and current meter
readings from the dc distribution panel meters.
____
2)
Take and record the Battery Room ambient temperature.
Acceptance Criteria: Temperature recorded correctly.
(15 C to 35 C)
____
3)
Check and record the battery (as found) terminal voltage, using a digital
voltmeter and reading at the battery terminals.
____
CAUTION:
Do not allow charger output to exceed XX amps.
4)
If battery terminal voltage is outside the XXX to XXX volt range, adjust the
charger to obtain XXX to XXX volts and record the battery terminal voltage
(as left).
Acceptance Criteria: Adjustment made and readings (as left) correctly
recorded. (XXX-XXX Vdc)
____
5)
Check and record the charger (As Left) voltage and current meter readings
from the dc distribution panel.
Acceptance Criteria: Readings recorded correctly.
____
(XXX-XXX- Vdc) ( X amps)
NOTE: A table providing manufacturer's correction factors for determining corrected
specific gravity (corrected for temperature and level) should be provided with
procedure.
6)
Take and record the following Pilot cell parameters:
- Pilot cell number
- Hydrometer reading (HYD)
- Pilot cell temperature (TEMP) and temperature correction factor
- Electrolyte level (LEVEL) and level correction factor
- Pilot cell voltage (VOLTS).
____
Completed by ____________________________________ Date_______
/
(signature)
(print name)
7)
Inspector shall verify that the values obtained are correct and that
acceptance criteria are met in Steps C.1 through C.6.
Verified by ______________________________________ Date_______
/
(signature)
(print name)