TABLE I. Typical Lead-Acid Battery/Cell Surveillance and Tests
Subject (Note 3)
Values (Note 1)
Period
Battery Terminal Voltage (typical 60
(129-130.2) volts PbSb
monthly
cell battery)
(130.2-135) volts PbCa
Electrolyte Level
Between fill lines (distilled
monthly
water only)
Cell Float Voltage
(2.15-2.17) volts PbSb
monthly
(Pilot cell)
(2.17-2.25) volts PbCa
Cell Float Voltage
(2.15-2.17) volts PbSb
quarterly
(All cells)
(2.17-2.25) volts PbCa
Specific Gravity
1.215 0.010
monthly
(Pilot cell)
Specific Gravity
1.215 0.010
quarterly
(All cells)
Cleanliness and Corrosion Check
(Note 2)
monthly
Resistance Measurement Cell to Cell
< 20% above the value
yearly
and Terminal Connections
when new or after cleaning
retorquing bolts
Battery Capacity Test
> 80% of capacity (Note 5)
5 years
(PERFORMANCE DISCHARGE TEST)
Battery Load Test
Design load and duration
yearly
(Service Test)
with adequate voltage
(Note 4)
Note 1 Values outside these ranges indicate action is necessary to restore the parameter
to within the specified values.
Note 2 Battery cleaning should be done with baking soda and water with clear water rinse--
no other cleaning materials shall be used.
Note 3 All manufacturer's safety precautions should be observed when working on
batteries.
Note 4 Not required where battery is for engine generator only and not other loads. The
periodic monthly start of the engine generator is a load test. Load tests should be
done in as-found condition.
Note 5 Battery capacity (performance discharge) test is used as a battery age indicator.
Initially, battery should be fully charged, temperature near 25 C, and terminals
clean. See IEEE Std 450 for times the battery capacity test should be performed.