| DOE-STD-3025-99
3.16
Penetrometer
A machine for determining test aerosol penetration and airflow resistance of HEPA
filters which incorporates an approved aerosol and aerosol generator, a penetration
meter, manometers for measuring resistance to airflow, a flow meter for determining test
airflow, and a chuck assembly for encapsulating and holding the filter under test.
3.17
Preparing Activity
The DOE organization responsible for issue and interpretation of this standard.
3.18
Standard Orifice Plate
A secondary standard for measuring airflow through the Penetrometer. Orifice plates
shall be calibrated using a National Institute of Standards Technology (NIST) traceable
standard as a primary standard.
3.19
Test Aerosol
The aerosol produced from a substance approved by DOE for testing HEPA filters.
4.
GENERAL PROVISIONS
Each HEPA filter procured for installation in a DOE nuclear facility shall be submitted for
testing at a Filter Test Facility (FTF). The tests are performed in accordance with section 5 of
this standard, the customer's written specifications or procurement documents, and any special
written instructions from the customer. Unless otherwise instructed, FTF tests and inspections
shall include:
C
Visual inspection for compliance with purchase order, e.g., type, size, quantity received,
shipping damage, and Qualification Certification.
C
Visual inspection for manufacturing defects and compliance with construction and
materials requirements.
C
Penetration at 100% (all filters) and penetration at 20% (size 3 and higher) of nominal
airflow rating.
C
Airflow resistance at 100% of test airflow.