DOE-SPEC-3019-96
ATTENTION:
Include optional method of marking, if desired.
********************
3.7.1
Nameplate. Provide a corrosion-resistant nameplate with clearly legible writing
for each jar, in an easily visible place. It shall provide all necessary information
pertaining to the equipment but, as a minimum, include the following:
manufacturer's name, type of battery cell, manufacturer's type designation,
nominal electrolyte specific gravity at 77F (25C) and date of manufacture.
[Alternately, the date of manufacture may be stamped on one of the jar posts.]
Polarity markings. For each battery cell, the positive posts shall be marked
3.7.2
either with a positive sign (+) or letters "POS." Negative posts shall carry a
negative sign (-) or the letters "NEG."
ATTENTION:
Where applicable, include the following paragraph and enter the seismic zone number for the battery installation.
********************
3.7.3
Seismic qualification marking. Mark each rack "Zone [
]."
ATTENTION:
Revise scope of field services as appropriate, depending on who does the installation.
********************
Installation. The [Owner will] [Seller shall] install the batteries. [Provide the services of a
field-service representative to provide technical advice for installation and startup. Scope
of services shall be clearly stated in Seller's proposal in accordance with Appendix A.]
Provide adequate information covering installation requirements in time for Owner's use
(see paragraph 4.4).
ATTENTION:
Include the following paragraph if an annual maintenance contract is required. Coordinate with Appendix A
requirements.
********************
Maintenance. Submit with the proposal a quotation for the annual maintenance of each
battery string. Include details of the maintenance work, testing and record-keeping
performed as a part of the maintenance contract. Submit with the proposal a typical
example of a maintenance report for a similar maintenance contract.
a. Submit the drawings and data required by the specification and/or listed in
paragraph 4.2 within the time specified for Owner's review.