| DOE-STD-3003-2000
B. INSPECTION AND CLEANING
1)
Check the battery cells for cracks and leakage of electrolyte.
____
2)
If cell cracks and leakage of electrolyte are found, note the location in the
Comments section of Data Sheet 1, complete an NCR, and notify Electrical
Supervision promptly.
____
3)
Check the intercell and terminal connections for corrosion.
____
4)
If any cell connections are corroded:
a)
Neutralize the corrosion with a neutralizing agent.
____
b)
Remove corrosion with stiff plastic bristled brush and clean rags.
____
c)
Note the location in the Comments section of the Data Sheet 1.
____
NOTE: Use water only as a cleaning agent; do not use hydrocarbon-type cleaning
agents or strong alkaline cleaning agents that may cause containers and
covers to crack or craze.
5)
Clean the battery and rack:
a)
Remove electrolyte spillage with clean rags and a neutralizing agent.
____
b)
Remove dirt from cells and rack using clean cloths dampened with
clean water.
____
6)
If protective grease was removed from intercell and terminal connections
during cleaning, apply a light coat of No-Ox-Id grease to the affected
terminal.
Section A completed by ______________________________________________
/
(signature)
(print name)
Date/Time Completed ____________________________ a.m./p.m.
/
:
26
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |